Can two switches share a neutral?

All switches on the same circuit share a neutral wire. Neutral wires for lighting is not switched and run from one bulb fixtures, to the next. The live wire run, daisy-chained, from switch to switch, and the switched live goes to the bulb fixture.
Takedown request View complete answer on quora.com

What happens if 2 circuits share a neutral?

Only if the breakers are tied together. The NEC requires that if two or 3 circuits have one neutral, thatall 2/3 breakers will shut down if one is turned off. The reason being that there will still be a load on the neutral making it a hazard.
Takedown request View complete answer on quora.com

Are you allowed to share neutrals?

Industry standards consider it especially bad practice to share neutrals for circuits intended for computer systems. Best-practice recommends that shared or common neutrals be sized up one gage of wire to reduce electrical noise and help prevent overcurrent scenarios.
Takedown request View complete answer on esgrounding.com

Can 2 neutrals go together?

Can you put 2 neutral wires together? - Quora. You can if they are both on the same circuit, or if the two circuits are different phases, though the second part may not be up to your local code. If they are on different circuits but the same phase, it might not be safe and definitely isn't to code.
Takedown request View complete answer on quora.com

Can a switched outlet share a neutral?

Can two different circuits share the same neutral wire (and breakers)? Yes, a multiwire branch circuit is two 120 volt circuits with a shared neutral conductor. A multiwire branch circuit can be connected from two adjacent single pole breakers with an approved handle tie OR a 2-pole breaker.
Takedown request View complete answer on quora.com

Neutral Imbalance in Multiwire Branch Circuits (Two Hots, One Neutral)

Can 2 circuits share a neutral on GFCI?

Will a GFCI work with a shared neutral? Yes. It will work all the time. It will keep tripping because the the return neutral current from the shared circuits will never match the load current in the phase conductor of the protected circuit.
Takedown request View complete answer on quora.com

Can a dedicated circuit share a neutral?

Depends. If the neutrals are from 2 different phases, then you can. Sharing neutrals use to be common until a code change a few years ago. However, if the hots are from the same phase, but on different breakers, then no.
Takedown request View complete answer on quora.com

How many circuits can share a neutral?

The reason for this is that the active circuit can deliver return current through the neutral, and if it is disconnected (presumably by an electrician while repairing or adding devices), it can cause a shock. Needless to say, it's never safe or legal to have more than 2 circuits connected to the same return neutral.
Takedown request View complete answer on quora.com

Can 2 20 amp circuits share a neutral?

Yes, you can share the same white for neutral on both circuits, you must use a double pole breaker or two adjacent single pole breakers with a handle tie, and your wiring must be done such that removing a device doesn't interrupt the neutral - in other words, pigtail the neutrals.
Takedown request View complete answer on diy.stackexchange.com

Does each electrical circuit need its own neutral?

Their are still millions upon millions of circuit breakers that share a neutral. It's been a common practice for many years and still is in many jurisdictions across the nation. How ever the NEC has now required the circuits sharing a neutral. They must all be able to be turned off with one breaker.
Takedown request View complete answer on forums.mikeholt.com

Can 2 neutrals share a lug?

NO, NEVER..!! in any panel, only ONE neutral wire per terminal is allowed to be terminated on one terminal,.. bare ground wires can be bundled (2 to 3) and share a terminal on the neutral/ground bar in a MAIN PANEL..and grounds must be terminated to the separate ground bar in a sub panel.
Takedown request View complete answer on quora.com

Why can't you switch neutrals?

If, however, the "neutral" is switched, there would always be a voltage potential at the fixture or device. A safe path for current to flow only exists when the switch is closed. In this situation you could potentially become the path to ground, especially when the switch is off.
Takedown request View complete answer on diy.stackexchange.com

Why do I have 2 neutral wires?

It's old school wiring, a variation of the loop in system that was used in conduit. You will find at each light one or two neutrals and at each switch one or two phases (red switch feeds) and another red going off to the light (a red switch wire).
Takedown request View complete answer on community.screwfix.com

Can 3 120v circuits share a neutral?

If you add a 3rd circuit and say you had 20A and 15A on PhaseA, and 10A on PhaseB, you would have 20+15-10=25A on the neutral. This would overload the neutral. That's why you can't have more than two circuits sharing a neutral.
Takedown request View complete answer on justanswer.com

Can you tie all neutrals together from different circuits?

You can if they are both on the same circuit, or if the two circuits are different phases, though the second part may not be up to your local code. If they are on different circuits but the same phase, it might not be safe and definitely isn't to code.
Takedown request View complete answer on quora.com

Can a neutral wire be overloaded?

Yes, multiwire circuits offer fewer conductors, reduced raceway size and reduced circuit voltage drop; however, improper wiring or mishandling of multiwire circuits can cause overloading of the grounded (neutral) conductor and/or destruction of equipment.
Takedown request View complete answer on mikeholt.com

How many amps is a shared neutral?

An ordinary 120V circuit has a ground, neutral and hot conductor. With 12 AWG wire, it can deliver 20 amps. A shared neutral circuit has an additional hot conductor, which is connected to the opposing phase. This allows a further 20 amps to be delivered, with the addition of only one conductor.
Takedown request View complete answer on instructables.com

How does 220V work without a neutral?

Evidently 220V circuits do not need a neutral because two hot wires belong to the same circuit. And because they take turns and do not combine on the same cycle, their amplitudes differ but combine mutually in phasor angulation to arrive at 110V total complement, apiece (220 V).
Takedown request View complete answer on quora.com

Can I connect neutral and ground together?

Summary. Proper grounding is essential for safety and good power quality. Neutral is the return path of the current, and ground wire holds the fault current to trip the breaker in protecting the person and the facility. The neutral and ground should never be bonded together in the facility except for the main panel.
Takedown request View complete answer on ep2000.com

What is a split neutral?

The split Nuetral is refering to using the same nuetral for both A/B phases.. You will most likely see white and green wires in the same bus as well as two nuetral busses that are bonded together with a copper peg.
Takedown request View complete answer on garagejournal.com

Does a GFCI need its own neutral?

No, it is not possible to use a GFCI (Ground Fault Circuit Interrupter) breaker without a neutral wire. GFCI devices work by comparing the current going out on the hot wire with the current returning on the neutral wire.
Takedown request View complete answer on quora.com

Can you put 2 neutral wires together in panel?

Those two different wire sizes also present a torquing issue, where one will not have a good connection. Any panel installed after 2002, it is a no brainer that double tapped neutrals are not allowed, with concrete evidence of this in the NEC, but it is still common to see them double tapped.
Takedown request View complete answer on southernsourceinspections.com

Is it OK to have 2 GFCI on same circuit?

Either way, it is OK. But in the case of the ones wired in series, the second one will not offer any more protection so its a waste of money. The first GFCI would protect all downstream outlets. Moreover, you might have to reset both if there was a fault downstream of the second one.
Takedown request View complete answer on quora.com

What happens if you don't connect neutral wire?

Loss of neutral is a serious condition. A break in the neutral conductor will simply result in a loss of the energy supply which leads to an Irrespective of load balance.
Takedown request View complete answer on sollatek.com

What can I do with extra neutral wire?

Two choices:
  1. You simply connect it to all the other neutrals and no one will notice for decades. But you don't know what the other end of that neutral is connected to, so Option 2 is better.
  2. You cap it off by itself and any electrician who notices it will wonder why but leave it alone as long as everything works.
Takedown request View complete answer on quora.com